Description
DC System Voltage (V) | 24 | 48 | 60 | 110 | 125 | 220 |
Module rating (A) | 75 | 42/62.5 | 42 | 20 | 20 | 10 |
Max Standard rating (A) | 1500 | 840/1250 | 840 | 400 | 400 | 200 |
Input
Input voltage | 220/230/240 Vac 1-phase ±10%, / 380/400/415 Vac 3-phase ±10%, 50/60 Hz ±10% | |||||
Power factor/Input THDi | 0,99 @ 50% – 100% Load / THDi < 5% @ 100% Load |
Output
DC Voltage range (V) | 21.7–28.8 | 7.6 | 54-72 | 89.2-171.6 | 89.2-171.6 | 178.5-297 |
Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
System
Cooling | Forced cooled modules | |||||
Colour | RAL 7035 (others on request) | |||||
Protection degree (IEC 60529) | IP 20 standard (optional up to IP 54) | |||||
Output Ripple | < 2% @ Full Load | < 1% @ Full Load | ||||
Efficiency | > 92% @ Full Load | > 94% @ Full Load | ||||
Options | LED mimic. Customizable status and alarms LED set |
Environmental
Operating temperature | -10 °C ÷ +40 °C (optional up to 55°C with derating) / Storage temperature: -20 °C ÷ +70 °C | |||||
Altitude | < 2000 m (derating according to EN 62040-3) | |||||
Audible noise at 1 meter (dBA) | ≤ 65 |
User Interface
Front panel | LCD display, keyboard |
Standards
Test and performance | IEC EN 60146-1-1 |